SEC 1500 Gas Detector
The SEC 1500 Gas Detector is a digital
gas detector designed to detect one of
a number of gases, display the concentration
of that particular gas, and provide an
alarm when gas concentrations reach preset
levels.
The SEC 1500 will operate as a stand-alone
gas detector with independent relay outputs
and LED display. An industry standard
4-20 mA output enables the SEC 1500
to be connected to existing analog systems.
The SEC 1500 operating parameters (relay
action, alarm set values, sensor configuration,
etc.) can be viewed or changed using the
SEC 2500 Hand Held
Programmer. This device can communicate
anywhere on the network with any SEC 1500
by connecting to the RS-485 data highway.
An RS-485 digital output enables the SEC
1500 to communicate to the SEC 4100 System
Monitor or a personal computer running
SEC
Supervision Plus software. The network
is formed by connecting a single twisted
shielded pair cable of wires, reducing
cabling and installation costs compared
to traditional analog systems.
The SEC 1500 retains operating parameters
and calibration settings when powered
down. An onboard microprocessor provides
continuous self-diagnostics and identifies
problems using fault codes. Four optional
8 amp SPDT relays respond to low, mid,
and high gas alarms as well as any fault
conditions.
The SEC 1500 is network compatible with
the SEC 2000 Gas
Detector, the SEC
IR Detector, SEC
Supervision Plus software, the Digital
Analog Interface Module (DAIM), SEC
4100 System Monitor and the Expansion
Relay Controllers.
SEC 1500 Gas Detector Features
| |
Designed
for non-hazardous environments |
| |
Low-cost
installation |
| |
Over
20 different gases detected |
| |
120
VAC, 220 VAC or 10-30 VDC operation
models available |
| |
CSA/NRTL
approved |
| |
Industry
standard 4-20 mA output |
| |
RS-485
digital output |
| |
Optional
programmable relays |
| |
User
friendly, one person calibration |
| |
Provides
continuous self-diagnostics |
| |
Toxic
and oxygen deficiency detectors |
| |
Retains
operating parameters and calibration
settings when powered down |
| |
Operates
with SEC
Supervision Plus hazard
event monitoring software |
|
|

|
SEC 1500 Gas Detector Applications
| |
Petrochemical
Refineries |
|
Buildings |
|
Water
Treatment Plants |
| |
Compost
Facilities |
|
Tunnels |
|
Parking
Garages |
| |
Semi-Conductor
Industry |
|
Automotive
Industry |
|
Chemical
Industry |
| |
Mining |
|
Engine
Test Rooms |
|
Nuclear
Industry |
| • |
Pulp
and Paper Mills |
• |
Air
Quality Intake System |
|
Medical
Facilities |
| • |
Refrigeration
Applications |
• |
Sewage
Industry |
|
Fertilizer
Industry |
SEC 1500 Gas Detector Specifications
| ALARMS |
|
Visual
indication and relay contacts for
low, mid, high and fault |
 |
| APPROVAL |
|
CSA
file # LR 95495-6 |
 |
| DETECTION
METHOD |
|
Toxic
Gases Electrochemical
Oxygen Galvanic |
 |
| ENCLOSURE
CONSTRUCTION |
|
NEMA
4 powder coated steel enclosure
NEMA 4X 12 & 13 molded fiberglass,
or
NEMA 4X 12 & 13 304 stainless
steel |
 |
| ENCLOSURE
DIMENSIONS |
|
6
(W) x 9.5 (L) x 3.8 (H) inches |
 |
| OPERATING
VOLTAGE |
|
120
or 220 VAC
10-30 VDC |
 |
| ANALOG
OUTPUT |
|
4-20
mA (source type), max. 1,000 ohm load
at 24 VDC supply voltage |
 |
| DIGITAL
OUTPUT |
|
RS-485
LAN |
 |
| RELAY
OPERATION |
|
Selectable
latching or non-latching
Selectable normally energized or normally
de-energized (except fault)
Selectable alarm relay off delays
Manual relay control |
 |
| RELAY,
TYPE AND RATING |
|
SPDT:
8 Amps at 250 VAC, 8 Amps at 30 VDC |
 |
| TEMPERATURE
RANGE |
|
-20º
to +50º C |
 |
| WEIGHT |
|
Approximately
7 lbs. (3.2 Kg.) |
|
|